Features & Specification
Universal AC input/Full range
Protection:Short circuit / over load
Approval:CE
100% full load burn-in test
High reliability,low cost
2 years warranty
|
INDEX TYPE
|
S-25-5
|
S-25-12
|
S-25-15
|
S-25-24
|
|
DC VOLTAGE
|
5V
|
12V
|
15V
|
24V
|
|
VOLTAGE TOLERANCE
|
±2%
|
±1%
|
±1%
|
±1%
|
|
RATED CURRENT
|
5A
|
2.1A
|
1.7A
|
1.1A
|
|
CURRENT RANGE
|
0-5A
|
0-2.1A
|
0-1.7A
|
0-1.1A
|
|
RIPPLE&NOISE (MAX.)
|
50mVp-p
|
100mVp-p
|
100mVp-p
|
100mVp-p
|
|
LINE REGULATION
|
±0.5%
|
±0.5%
|
±0.5%
|
±0.5%
|
|
LOAD REGULATION
|
±1%
|
±0.5%
|
±0.5%
|
±0.5%
|
|
RATED POWER
|
25W
|
25.2W
|
25.5W
|
26.4W
|
|
EFFICIENCY
|
72%/115VAC
|
76%/115VAC
|
77%/115VAC
|
80%/115VAC
|
|
VOLTAGE ADJ.RANGE
|
+10 -5%
|
±10%
|
±10%
|
±10%
|
|
VOLTAGE RANGE
|
85~264VAC 47~63Hz
|
|
AC CURRENT
|
0.6A/115V 0.35A/230V
|
|
INRUSH CURRENT (MAX.)
|
cold inrushed currentt 15A/115V 30A/230V
|
|
LEAKAGE CURRENT
|
<0.75mA/240VAC
|
|
OVERLOAD PROTECTION
|
105%~150%TYPE:OUTPUT CUTOUT auto recovery
|
|
OVERVOLTAGE PROTECTION
|
115%-135%
|
|
TEMP.COEFFICIENT
|
±0.03%/℃(0~50℃)
|
|
SETUP.RISE,HOLD TIME
|
800ms,50ms,10ms/115VAC 300ms,50ms,80ms/230VAC
|
|
VIBRATION
|
10~500Hz,2G 10min,/1cycle,60min,each axes
|
|
WITHSTAND VOLTAGE
|
I/P-O/P:3KVACI/P-FG:1.5KVACO/P-FG:0.5KVAC
|
|
ISOLATED RESISTOR
|
I/P-O/P,I/P-FG,O/P-FG:500VDC/100MΩ
|
|
WORKING TEMP.HUMIDITY
|
-10℃~+60℃(REFER TO CHARACTER CURVE),20%~90RH
|
|
STORAGE TEMP.HUMIDITY
|
-20℃~+85℃,10%~95%RH
|
|
DIMENSION
|
99×97×35mm
|
|
WEIGHT
|
0.37Kgs
|
|
SAFETY STANDARDS
|
To meet TUV EN60950 , CE
|
|
EMC
|
CISPR22(55022),IEC801-2,3,4,IEC555-2
|
|
|
Note:
|
|
|
1.All parameters NOT specially mentioned are measured at 230VAC input ,rated load and 25 of ambient temperature.
2.Tolerance:includes set up tolerance, line regulation and load regulation
3.Ripple&noise are measured at 20MHZ of bandwidth by using a 12 twisted pair-wire terminated with a 0.1uf&47uf parallel capacitor.
4.line regulation :min&max voltage of the rated load.
5.load regulation: load from 0 to 100%.
|